All Ri-Cycle waste water treatment systems have the following features:
  • Lowara stainless steel delivery pumps
  • High quality Teflon coated Air Diffusers.
  • High grade Filter Medium
  • Stainless steel internal anchors
  • High quality dosing pumps

Specifications for EP20

Primary septic capacity: 12000 ltr
Aerated chamber capacity: 6,516 ltr
Combined clarifier pump out chamber capacity: 2,113 ltr
Air blower: Elmo Reitschle SAH 0045, 4.3 amp, 1 phase 3 phase avail
Air diffusers: 5 no. 270mm dia. SSI Airflex fine bubble diffusers
Irrigation pump: Max 240 lpm Max Head 14m 240 VOLT 550W lowara 07 water pump standard
Chlorinator: Liquid Sodium Hypochlorite dosing system with Acromet BH-22 Auto dosing pump
Alarm system: Ri-Industries sight and sound warning of air pressure drop and high water level in Pump Out Chamber.

Final effluent quality: A properly maintained plant produces treated water of a very high quality.

 

As a minimum standard required by the Department of Health and other Health agencies the following standards apply:
  • BOD5 – less than 20mg/L
  • Suspended Solids – less than 30mg/L
  • Free residual chlorine – min 0.5mg/L
  • Faecal Coliforms – not more than 10 per 100ml

Specifications for EP30

Primary septic capacity: 20000 ltr
Aerated chamber capacity: 6,516 ltr
Combined clarifier pump out chamber capacity: 2,113 ltr
Air blower: Elmo Reitschle SAH 0055, 0.75kW, 6.9 amp 1 phase 3 phase avail
Air diffusers: 6 no. 270mm dia. SSI Airflex fine bubble diffusers
Irrigation pump: Max 240 lpm Max Head 14m 240 VOLT 550W lowara 07 water pump standard
Chlorinator: Liquid Sodium Hypochlorite dosing system with Acromet BH-22 Auto dosing pump
Alarm system: Ri-Industries sight and sound warning of air pressure drop and high water level in Pump Out Chamber.

Final effluent quality: A properly maintained plant produces treated water of a very high quality.

 

As a minimum standard required by the Department of Health and other Health agencies the following standards apply:
  • BOD5 – less than 20mg/L
  • Suspended Solids – less than 30mg/L
  • Free residual chlorine – min 0.5mg/L
  • Faecal Coliforms – not more than 10 per 100ml

Specifications for EP40

Primary septic capacity: 20000 ltr
Aerated chamber capacity: 6,516 ltr
Combined clarifier pump out chamber capacity: 2,113 ltr
Air blower: Elmo Reitschle SAH 0045, 0.75kW, 6.9 amp 1 phase 3 phase avail
Air diffusers: 6 no. 270mm dia. SSI Airflex fine bubble diffusers
Irrigation pump: Max 240 lpm Max Head 14m 240 VOLT 550W lowara 07 water pump standard
Chlorinator: Liquid Sodium Hypochlorite dosing system with Acromet BH-22 Auto dosing pump
Alarm system: Ri-Industries sight and sound warning of air pressure drop and high water level in Pump Out Chamber.

Final effluent quality: A properly maintained commercial waste water treatment system produces treated water of a very high quality.

 

As a minimum standard required by the Department of Health and other Health agencies the following standards apply:
  • BOD5 – less than 20mg/L
  • Suspended Solids – less than 30mg/L
  • Free residual chlorine – min 0.5mg/L
  • Faecal Coliforms – not more than 10 per 100ml